Przeglądanie stron 262
Parameter listing and descriptions 259
ACH550-01 User's Manual
Group 36: TIMED FUNCTIONS
This group defines the timed functions. The timed functions
include:
four daily starts/stops
four weekly starts/stops, overrides
four timers for collecting selected periods together.
A timer can be connected to multiple time periods and a time
period can be in multiple timers.
TIME PERIOD 1
3602 START TIME 1
3603 STOP TIME 1
3604 START DAY 1
3605 STOP DAY 1
TIME PERIOD 4
3614 START TIME 4
3615 STOP TIME 4
3616 START DAY 4
3617 STOP DAY 4
TIME PERIOD 3
3610 START TIME 3
3611 STOP TIME 3
3612 START DAY 3
3613 STOP DAY 3
TIME PERIOD 2
3606 START TIME 2
3607 STOP TIME 2
3608 START DAY 2
3609 STOP DAY 2
BOOSTER
3622 BOOST SEL
3623 BOOST TIME
TIMER 1
3626 TIMER 1 SRC
TIMER 2
3627 TIMER 2 SRC
TIMER 3
3628 TIMER 3 SRC
TIMER 4
3629 TIMER 4 SRC
DI1…DI6
DI1(INV)…DI6(INV)
Activates boost
Przeglądanie stron 262
1 2 ... 258 259 260 261 262 263 264 265 266 267 268 ... 473 474

Komentarze do niniejszej Instrukcji

Brak uwag

Ashly Receptores y amplificadores manuales de usuario

Empezando en C

Haga clic en el alfabeto a continuación para desplazarse a la lista completa de modelos que comienzan con esa letra

Modelos Tipo de documento
Compressor/Limiter CL-52
Manual de usuario   Ashly Compressor/Limiter CL-52 User Manual, 2 paginas
Crossover XR Series
Manual de usuario   Ashly Crossover XR Series User Manual, 1 paginas