Air flow, 380…480 V drives
The following table lists heat loss and air flow data for
380…480 V drives at full load.
Drive Heat loss Air flow
ACH550-01- Frame size W BTU/hr m
3
/h ft
3
/min
02A4-4 R1 30 101 44 26
03A3-4 R1 40 137 44 26
04A1-4 R1 52 178 44 26
05A4-4 R1 73 249 44 26
06A9-4 R1 97 331 44 26
08A8-4 R1 127 434 44 26
012A-4 R1 172 587 44 26
015A-4 R2 232 792 88 52
023A-4 R2 337 1151 88 52
031A-4 R3 457 1561 134 79
038A-4 R3 562 1919 134 79
045A-4 R3 667 2278 134 79
059A-4 R4 907 3098 280 165
072A-4 R4 1120 3825 280 165
087A-4 R4 1440 4918 280 165
125A-4 R5 1940 6625 350 205
157A-4 R6 2310 7889 405 238
180A-4 R6 2810 9597 405 238
195A-4 R6 3050 10416 405 238
246A-4 R6 3260 11133 405 238
290A-4 R6 3850 13125 405 238