ABB RCNA-01 Instrukcja Użytkownika Strona 221

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 474
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 220
Parameter listing and descriptions 217
ACH550-01 User's Manual
2013 MIN TORQUE SEL -6…7
Defines control of the selection between two minimum torque limits
(2015
MIN TORQUE 1 and 2016 MIN TORQUE 2).
0 =
MIN TORQUE 1 – Selects 2015 MIN TORQUE 1 as the minimum limit
used.
1 =
DI1 – Defines digital input DI1 as the control for selecting the
minimum limit used.
• Activating the digital input selects
MIN TORQUE 2 value.
• De-activating the digital input selects
MIN TORQUE 1 value.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the control for
selecting the minimum limit used.
•See
DI1 above.
7 =
COMM – Defines bit 15 of Command Word 1 (parameter 0301) as the
control for selecting the minimum limit used.
• The Command Word is supplied through fieldbus communication.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as the control for
selecting the minimum limit used.
• Activating the digital input selects
MIN TORQUE 1 value.
• De-activating the digital input selects
MIN TORQUE 2 value.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6
as the control for selecting the minimum limit used.
•See
DI1(INV) above.
2014 MAX TORQUE SEL -6…7
Defines control of the selection between two maximum torque limits
(2017
MAX TORQUE 1 and 2018 MAX TORQUE 2).
0 =
MAX TORQUE 1 – Selects 2017 MAX TORQUE 1 as the maximum limit
used.
1 =
DI1 – Defines digital input DI1 as the control for selecting the
maximum limit used.
• Activating the digital input selects
MAX TORQUE 2 value.
• De-activating the digital input selects
MAX TORQUE 1 value.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the control for
selecting the maximum limit used.
•See
DI1 above.
7 =
COMM – Defines bit 15 of Command Word 1 (parameter 0301) as the
control for selecting the maximum limit used.
• The Command Word is supplied through fieldbus communication.
-1 =
DI1(INV) – Defines an inverted digital input di1 as the control for
selecting the maximum limit used.
• Activating the digital input selects
MAX TORQUE 1 value.
• De-activating the digital input selects
MAX TORQUE 2 value.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6
as the control for selecting the maximum limit used.
•See
DI1(INV) above.
2015 MIN TORQUE 1 -600.0…0%
Sets the first minimum limit for torque (%). Value is a percentage of the
motor nominal torque.
Code Description Range
Przeglądanie stron 220
1 2 ... 216 217 218 219 220 221 222 223 224 225 226 ... 473 474

Komentarze do niniejszej Instrukcji

Brak uwag