Serial communications 137
ACH550-01 User's Manual
(3AFE68320658 [English]) and BACnet® Protocol
(3AUA0000004591 [English]).
The communication between the drive and the fieldbus is then
activated by selecting the appropriate protocol with parameter
9802
COMM PROT SEL. After the communication is initialized, the
configuration parameters become available in parameter Group
53: EFB PROTOCOL in the drive.
Setting up EFB with the Serial Communication assistant is
shown below. The related parameters are described starting
from page 138.
For BACnet/IP, follow the instructions in RBIP-01 BACnet/IP
Router Module Installation Manual (3AUA0000040168 [English])
and RBIP-01 BACnet/IP Router Module User’s Manual
(3AUA0000040159 [English]).
Setting up EFB with the Serial Communication assistant
To set up EFB, follow these steps:
1 Press MENU to go to the
main menu.
2 Select ASSISTANTS with
the UP/DOWN keys and
press ENTER.
3 Scroll to Serial
Communication and press
SEL.
4 Select the protocol with the
UP/DOWN keys and press
SAVE.
0 A
0 Hz
0 %0.
0.
0.
0.0Hz
OFF
MENU
00:00
PARAMETERS
ASSISTANTS
CHANGED PAR
EXIT ENTER00:00
OFF
MAIN MENU 2
Low Noise Set-up
Panel Display
Timed Functions
Outputs
Serial Communication
EXIT
SEL
00:00
ASSISTANTS 14
OFF
9802 COMM PROT SEL
PAR EDIT
BACNET
[5]
OFF
EXIT SAVE
00:00