ABB RCNA-01 Instrukcja Użytkownika Strona 218

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 474
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 217
214 Parameter listing and descriptions
ACH550-01 User's Manual
1706 OVERRIDE DIR -6…7
Selects the source of the override direction signal.
0 =
FORWARD – Assigns forward as the override direction.
1 =
DI1 – Defines digital input DI1 as the override direction signal.
• De-activating the digital input selects the forward direction.
• Activating the digital input selects the reverse direction.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the override direction
signal.
•See
DI1 above.
7 =
REVERSE – Assigns reverse as the override direction.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as the override
direction signal.
• Activating the digital input selects the forward direction.
• De-activating the digital input selects the reverse direction.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6
as the override direction signal.
•See
DI1(INV) above.
1707 OVERRIDE REF 1=CONSTANT, 2=PID
Selects the source of the override reference.
1 =
CONSTANT – Selects a preset frequency or speed for the override.
The frequency value is defined by parameter 1702
OVERRIDE FREQ
and the speed value by parameter 1703
OVERRIDE SPEED.
2 =
PID – The reference is taken from the PID output, see group 40
PROCESS PID SET 1.
Note: The following conditions must be met when using PID in the
override mode:
• PID1 set point (parameter 4010
SET POINT SEL) can be either A1, A2
or
INTERNAL.
• PID1 parameter set 1 must be active (parameter 4027
PID 1 PARAM
SET = SET 1).
• Override direction (parameter 1706
OVERRIDE DIR) can be either
0(
FORWARD) or 7 (REVERSE).
Code Description Range
Przeglądanie stron 217
1 2 ... 213 214 215 216 217 218 219 220 221 222 223 ... 473 474

Komentarze do niniejszej Instrukcji

Brak uwag