Parameter listing and descriptions 193
ACH550-01 User's Manual
Group 13: ANALOGUE INPUTS
This group defines the limits and the filtering for analogue inputs.
Code Description Range
1301 MINIMUM AI1 0…100%
Defines the minimum value of the analogue input.
• Define value as a percentage of the full analogue signal range. See
example below.
• The minimum analogue input signal corresponds to 1104
REF1 MIN or
1107
REF2 MIN.
•
MINIMUM AI cannot be greater than MAXIMUM AI.
• These parameters (reference and analogue min. and max. settings)
provide scale and offset adjustment for the reference.
• See the figure for parameter 1105.
Example. To set the minimum analogue input value to 4 mA:
• Configure the analogue input for 0…20 mA current signal.
• Calculate the minimum (4 mA) as a percentage of the full range
(20 mA) = 4 mA / 20 mA · 100% = 20%
1302 MAXIMUM AI1 0…100%
Defines the maximum value of the analogue input.
• Define value as a percentage of the full analogue signal range.
• The maximum analogue input signal corresponds to 1105
REF1 MAX
or 1108
REF2 MAX.
• See the figure for parameter 1105.
1303 FILTER AI1 0…10 s
Defines the filter time constant for analogue input 1 (
AI1).
• The filtered signal reaches 63% of a step change within the time
specified.
1304 MINIMUM AI2 0…100%
Defines the minimum value of the analogue input.
•See
MINIMUM
AI
1 above.
100
63
[%]
Unfiltered signal
Filtered signal
Time constant
t