ABB RCNA-01 Instrukcja Użytkownika Strona 278

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 474
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 277
274 Parameter listing and descriptions
ACH550-01 User's Manual
4006 UNIT 0…127
Selects the unit for the PID controller actual values. (PID1 parameters
0128, 0130 and 0132).
See parameter 3405 for list of available units.
4007 UNIT SCALE 0…4
Defines the decimal point location in PID controller actual values.
Enter the decimal point location counting from the right end of the
entry.
See the table for an example using pi (3.14159).
4008 0% VALUE unit and scale defined
by par. 4006 and 4007
Defines (together with the next parameter) the scaling applied to the
actual values of the PID controller (PID1 parameters 0128, 0130 and
0132).
Units and scale are defined by parameters 4006 and 4007.
4009 100% VALUE unit and scale defined
by par. 4006 and 4007
Defines (together with the previous parameter) the scaling applied to
the actual values of the PID controller.
Units and scale are defined by parameters 4006 and 4007.
Code Description Range
4007 Value Entry Display
0000033
1 00031 3.1
2 00314 3.14
3 03142 3.142
4 31416 3.1416
Internal scale (%)
P 4009
P 4008
100%
0%
Units (P4006)
Scale (P4007)
-1000.0%
+1000.0%
Przeglądanie stron 277
1 2 ... 273 274 275 276 277 278 279 280 281 282 283 ... 473 474

Komentarze do niniejszej Instrukcji

Brak uwag