©ABB Ltd -30
Example System (Drive & Bypass) Monitoring / Control
Node No. 1
(5302 = 1)
Bypass Node
No. 2
(5002 = 2)
X:2, 27, 28,29
Bypass communications and/or control. 95 VFD & 45 bypass points
available
Siemens command points 24 & 60 come from Field Panel via FLN to
bypass X2: 28 & 29 and are routed to VFD and bypass
Siemens
Field
Panel
Node No. 3
(5302 = 3)
Bypass Node
No. 4
(5002 = 4)
X:2, 27, 28,29
Speed Ref.
= Siemens
point 60*
Start/Stop
= Siemens
point 24*
E-Clipse System 1
Ref. 1 =
Siemens
point 60*
Start/Stop
= Siemens
point 24*
E-Clipse System 2
Drive
Bypass
Drive
Bypass
Siemens FLN Example 1625 = 1 (system)
FLN
Komentarze do niniejszej Instrukcji