Starting up the FPBA-01 adapter for different communication profiles
25
*Read-only or automatically detected/set
**Example
The start sequence for the parameter example above is given below.
Control Word:
47Eh (1150 decimal) => READY TO SWITCH ON
47Fh (1151 decimal) => OPERATING (Speed mode)
C7Fh (3199 decimal)=> OPERATING (Torque mode).
53.02 FBA DATA OUT2 2 Reference 1
53.03 FBA DATA OUT3 3 Reference 2
51.27 FBA PAR REFRESH REFRESH Refreshing parameter settings of the
module