PROFIdrive parameters
115
970 R/W Unsigned16 Load parameter record
Value Description
0 No action
1 Restore factory settings
The parameter must do a zero-to-one
transition and the motor must be stopped.
971 R/W Unsigned16 Save parameter record
Value Description
0 No action
1 Save the drive parameters
to non-volatile memory
The parameter must do a zero-to-one
transition and the motor must be stopped.
972 R/W Unsigned16 Software reset
Value Description
0 No action
1 Re-boot PROFIBUS module
The parameter must do a zero-to-one
transition and the motor must be stopped.
* Read and/or Write
** Support depends on drive type
Para-
meter
R/W
*
Data type Description