The Analog Input Function Block can be mapped to one out of the five outputs channels from the Transducer Block
and makes this information available to other function blocks on the fieldbus network. The CHANNEL parameter
selects the input from the Transducer Block. Available channels include the primary process variable (Conductivity
when the PRIMARY_VALUE_TYPE is set to Conductivity or Concentration when the PRIMARY_VALUE_TYPE is set
to Concentration), temperature, and secondary process variable (Concentration when the PRIMARY_VALUE_TYPE
is set to Conductivity or Conductivity when the PRIMARY_VALUE_TYPE is set to Concentration).
The following diagram illustrates the Analog Input Function Block design. The following table lists the Analog Input
Function Block parameter information.
Transducer
Block
Sensor
AI Block
Channel Value
CHANNEL
Fieldbus
Acyclic
Channel Value
PV
(Conductivity or
Concentration)
Channel Value
SV1
(Temperature)
Channel Value
SV2
(Conductivity or
Concentration)
Block
Parameterization
TAG_DESC
STRATEGY
ALERT_KEY
GRANT_DENY
IO_OPTS
STATUS_OPTS
Simulation Enabled
SIMULATE
Percent Range Value
XD_SCALE
FIELD_VAL (%)
Linearization Type
L_TYPE
Output Scaling
OUT_SCALE
Indirect
Square Root Scaling
LOW_CUT
Direct Square Root
Damping
PV_FTIME
Direct
Block Mode
MODE_BLK
PV (Conductivity
or Concentration)
Alarm
Parameterization
UPDATE_EVT
BLOCK_ALM
ALARM_SUM
ACK_OPTION
ALARM_HYS
HI_HI_PRI
HI_HI_LIM
HI_PRI
HI_LIM
LO_PRI
LO_LIM
LO_LO_PRI
LO_LO_LIM
HI_HI_ALM
HI_ALM
LO_ALM
LO_LO_ALM
Alarm Detection
Acyclic
OUT
Cyclic Cyclic
Cyclic
Cyclic
Figure 32 – Analog Input Function Block Design Diagram