Installation of the drive connection
33
If you have a dual twisted pair cable, connect both wires of the second twisted pair to
ground.
The shields of all RS-485 network cables should be connected together. They
should be connected to only one device, for example the last drive of the network.
Connecting to multiple panel ports with RS-232/RS-485 converters
The panel ports of ACS350 and ACS/ACH550 drives, for example, communicate by
using the RS-232 protocol. Since RS-232 is designed only for point-to-point
applications, panel ports can not be used directly to connect multiple drives to
SREA-01. The communication protocol implementation of the panel ports, however,
supports multi-drop networks. Therefore it is possible to connect multiple drive panel
ports to a SREA-01 unit if standard RS-232/RS-485 converters are used.
To create a network of multiple drives by using panel ports, you need as many
RS-232/RS-485 converters as there are drives in your setup. Connect each panel
port to the RS-232 side of a converter and then connect the RS-485 sides to a
network. Attach the SREA-01 to this RS-485 network. See the following schematic.
SREA-01
B+
A-
COM
X1 RS-485
SHLD
DG
B
A
SHLD
DG
B
A
SHLD
DG
B
A
…
Terminating resistor
Drive 1 Drive 2 Drive N
Terminating resistor
120 ohm 120 ohm