ABB FENA-01 Instrukcja Użytkownika Strona 33

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 32
Installation of the drive connection
33
If you have a dual twisted pair cable, connect both wires of the second twisted pair to
ground.
The shields of all RS-485 network cables should be connected together. They
should be connected to only one device, for example the last drive of the network.
Connecting to multiple panel ports with RS-232/RS-485 converters
The panel ports of ACS350 and ACS/ACH550 drives, for example, communicate by
using the RS-232 protocol. Since RS-232 is designed only for point-to-point
applications, panel ports can not be used directly to connect multiple drives to
SREA-01. The communication protocol implementation of the panel ports, however,
supports multi-drop networks. Therefore it is possible to connect multiple drive panel
ports to a SREA-01 unit if standard RS-232/RS-485 converters are used.
To create a network of multiple drives by using panel ports, you need as many
RS-232/RS-485 converters as there are drives in your setup. Connect each panel
port to the RS-232 side of a converter and then connect the RS-485 sides to a
network. Attach the SREA-01 to this RS-485 network. See the following schematic.
Terminating resistor
Drive 1 Drive 2 Drive N
Terminating resistor
120 ohm 120 ohm
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Przeglądanie stron 32
1 2 ... 28 29 30 31 32 33 34 35 36 37 38 ... 102 103

Komentarze do niniejszej Instrukcji

Brak uwag