ACH550 for HVAC applications | ABB standard drives 7
W
H1
D
H2
D
W
H1
Technical data
Mains connection
Voltage and power
range
3-phase, 380 to 480 V, +10/-15% (0.75 to 355 kW)
3-phase, 208 to 240 V, +10/-15% (0.75 to 75 kW)
1-phase, 208 to 240 V, +10/-15% (50% derating)
auto-identification of in put line
Frequency
48 to 63 Hz
Power factor
0.98
Efficiency at rated power
98%
Motor connection
Voltage
3-phase, from 0 to U
N
Frequency
0 to 500 Hz
Rated currents
(apply to both IP21 and
IP54)
Current at ambient temperature of -15 to +40 °C:
rated output cur rent (I
2N
), no derating needed
Current at ambient temperature of +40 to +50 °C:
derating of less than 1%/ °C above 40 °C
Switching fre quen cy
Se lect able
0.75 to 37 kW: 1 kHz, 4 kHz, 8 kHz or 12 kHz
45 to 110 kW: 1 kHz, 4 kHz or 8 kHz
132 to 355 kW: 1 kHz or 4 kHz
Environmental limits
Ambient temperature
Transportation and
storage
Operation
-40 to 70 °C
-15 to 50 °C (no frost allowed)
Altitude
Output current
Relative humidity
Rated current available at 0 to 1000 m
reduced by 1% per 100 m over 1000 to 2000 m
2000 to 4000 m, please consult ABB
Lower than 95% (without con den sa tion)
Protection classes
IP21 or IP54
IP21 for wall mounted and free standing units
IP54 for wall mount ed units
Inputs and outputs
2 analog inputs
Volt age sig nal
Cur rent sig nal
Potentiometer reference
value
Selectable both for current and voltage
0 (2) to 10 V, R
in
> 312 kΩ single-ended
0 (4) to 20 mA, R
in
= 100 Ω single-ended
10 V ±2% max. 10 mA, R < 10 kΩ
2 analog outputs
Internal auxiliary voltage
0 (4) to 20 mA, load < 500 Ω
24 V DC ±10%, max. 250 mA
6 digital inputs
12 to 24 V DC with internal or ex ter nal supply
3 relay out puts
Maximum switch ing voltage 250 V AC / 30 V DC
Maximum con tin u ous current 2 A rms
PTC and PT 100
Any of the 6 digital in puts or an a log inputs can be
configured for PTC.
Both an a log outputs can be used to feed the PT
100 sensor.
Communication
Protocols as standard (RS 485): BACnet MS/TP,
Modbus RTU, N2 and FLN
Available as plug-in op tions: BACnet/IP router,
LonWorks, Ethernet etc.
Available as an external option: remote access
module
Protection functions
Overvoltage controller
Undervoltage controller
Earth-leak age su per vi sion
Motor short-circuit protection
Output and input switch su per vi sion
Overcurrent pro tec tion
Phase-loss detection (both mo tor and line)
Un der load su per vi sion - can be used also for
belt-loss detection
Overload su per vi sion
Stall protection
Product compliance
Harmonics
IEC/EN 61000-3-12
Standards and
directives
Low Voltage Di rec tive 2006/95/EC
Machinery Di rec tive 2006/42/EC
EMC Directive 2004/108/EC
Quality assurance system ISO 9001 and
Environmental system ISO 14001
CE, UL, cUL, and GOST R approvals
Gal van ic iso la tion according to PELV
RoHS (Restriction of Hazardous Substances)
EMC (ac cord ing to
EN61800-3)
Class C2 (1
st
en vi ron ment restricted distribution)
as standard
Types and ratings
P
N
kW
I
2N
A
Frame
size
Type designation
(order code)
U
N
= 380 to 480 V (380, 400, 415, 440, 460, 480 V)
HVAC control panel and EMC filter are included.
0.75 2.4 R1 ACH550-01-02A4-4
1)
1.1 3.3 R1 ACH550-01-03A3-4
1)
1.5 4.1 R1 ACH550-01-04A1-4
1)
2.2 5.4 R1 ACH550-01-05A4-4
1)
3 6.9 R1 ACH550-01-06A9-4
1)
4 8.8 R1 ACH550-01-08A8-4
1)
5.5 11.9 R1 ACH550-01-012A-4
1)
7.5 15.4 R2 ACH550-01-015A-4
1)
11 23 R2 ACH550-01-023A-4
1)
15 31 R3 ACH550-01-031A-4
1)
18.5 38 R3 ACH550-01-038A-4
1)
22 45 R3 ACH550-01-045A-4
1)
30 59 R4 ACH550-01-059A-4
1)
37 72 R4 ACH550-01-072A-4
1)
45 87 R4 ACH550-01-087A-4
1)
55 125 R5 ACH550-01-125A-4
1)
75 157 R6 ACH550-01-157A-4
1)
90 180 R6 ACH550-01-180A-4
1)
110 205 R6 ACH550-01-195A-4
1)
132 246 R6* ACH550-01-246A-4
1)
160 290 R6* ACH550-01-290A-4
1)
200 368 R8 ACH550-02-368A-4
250 486 R8 ACH550-02-486A-4
280 526 R8 ACH550-02-526A-4
315 602 R8 ACH550-02-602A-4
355 645 R8 ACH550-02-645A-4
Dimensions
Wall mounted units
Frame
size
Dimensions and weights
IP21 / UL type 1 IP54 / UL type 12
H1
mm
H2
mm
W
mm
D
mm
Weight
kg
H
mm
W
mm
D
mm
Weight
kg
R1 369 330 125 212 6,5 449 213 234 8.2
R2
469 430 125 222 9 549 213 245 11.2
R3 583 490 203 231 16 611 257 253 18.5
R4 689 596 203 262 24 742 257 284 26.5
R5 739 602 265 286 34 776 369 309 38.5
R6 880 700 302 400 69 924 410 423 80
R6* 986 700 302 400 73 1119 410 423 84
Free standing units
Frame
size
Dimensions and weights
H1
mm
H2
mm
W
mm
D
mm
Weight
kg
R8 2024 N/A 347 617 230
N/A = not applicable
H1 = Height with cable connection box
H2 = Height without cable connection box
W = Width
D = Depth
1)
This type code is valid for the IP21 unit. For the IP54 unit, add +B055 at
the end of the code.
I
2N
= Nominal output current 1,1 x I
2N
overload is allowed for 1 minute every 10
minutes through the entire speed range.
P
N
= Typical motor power. The ABB standard drive for HVAC can deliver P
N
continuously at an ambient temperature of 50
o
C.
U
N
= Nominal supply voltage
Komentarze do niniejszej Instrukcji